Tripping matrix to Generator Protection Systems

GKV 10x32 621 SK R ELDP
- 32 Input lines (columns)
- 32 Input discontinuity "E"
- 32 connecting plugs GSS-621/15 rt, red, 674.310.180.02
- 10 Output lines (rows)
- 2 rows Pin park
- Input- and Output signalling by LED indication (red) "L"
- Storing of LED indication by latching relays
- Group memory for storing of outgoing tripping signals
- LED-Reset push button
- LED-Test push button
- integrated test unit for diode plugs "D"
- 2 designation strips
- Power supply 250 VDC +/- 20%
- 19", 6U rack, front panel grey A281
- dorsal screw mount connectors, max. 4mm2 wire
- Acryl front cover, opening to the right "P"
GKV 10x32 621 SK R ELDP